BS EN 14470-2:2006 – Safety Cabinets for Pressurised Gas Cylinders

 

What does BS EN 14470-2 require for pressurised gas cylinder safety cabinets?

BS EN 14470-2:2006 sets performance and testing requirements for fire safety cabinets used for pressurised gas cylinders. It covers fire resistance, ventilation, cabinet construction, cylinder restraint and provisions for gas pipelines and electrical cables. The standard applies to qualifying indoor cabinets with a combined cylinder volume not exceeding 220 litres and does not replace the employer’s duties under DSEAR.

 

What is BS EN 14470-2?

BS EN 14470-2 is the British Standard for fire safety storage cabinets intended for pressurised gas cylinders.

The current edition is BS EN 14470-2:2006.

It is a product specification establishing performance requirements for the construction, ventilation and fire resistance of qualifying gas cylinder cabinets.

The standard is intended for cabinets used at normal room temperature and recognises that pressurised gas cylinders may remain connected and in use while housed within the cabinet.

 

Is BS EN 14470-2 still current?

Yes. BS EN 14470-2:2006 remains the current British Standard for fire safety storage cabinets for pressurised gas cylinders.

Unlike BS EN 14470-1, which was revised in 2023, BS EN 14470-2 remains at its 2006 edition.

 

Is BS EN 14470-2 a legal requirement in Great Britain?

No. BS EN 14470-2 is a product standard rather than a regulation requiring every gas cylinder to be stored in this type of cabinet.

Workplace risks involving flammable and other dangerous gases may instead create duties under legislation such as the Dangerous Substances and Explosive Atmospheres Regulations 2002 (DSEAR).

HSE guidance generally favours suitable outdoor storage for cylinders that are not in use because released gas can disperse more readily. Indoor storage may be appropriate where justified by safety, security or process requirements, but the quantities should be minimised and suitable fire-resistant, ventilated storage provided.

A BS EN 14470-2 cabinet can therefore form part of the controls selected through a workplace risk assessment but does not make the wider installation automatically compliant.

See our DSEAR Regulations 2002 guide for further information.

 

What size gas cylinder cabinet does BS EN 14470-2 cover?

BS EN 14470-2 applies to cabinets suitable for pressurised gas cylinders with a combined cylinder volume not exceeding 220 litres.

The standard gives examples equivalent to:

  • Up to four 50-litre gas cylinders.
  • Up to three 70-litre gas cylinders.

These examples describe the scope of the standard and should not be treated as a universal safe-storage allowance irrespective of the gases involved.

The actual number and type of cylinders should be determined from the cabinet specification, gas hazards, ventilation arrangements and workplace risk assessment.

 

What types of cabinet are covered by BS EN 14470-2?

Safety cabinets within the scope of BS EN 14470-2 may be:

  • Free-standing.
  • Restrained to a wall.
  • Mounted on wheels or castors.

The cabinet must take its weight on its base and meet the construction, ventilation and fire-performance requirements of the standard.

 

Does BS EN 14470-2 apply to gas cylinder cages or walk-in stores?

No. BS EN 14470-2 specifically excludes:

  • Brick enclosures.
  • Walk-in storage rooms.
  • Cabinets that do not take their weight on their base.

External gas cylinder cages, large purpose-built gas stores and walk-in storage facilities are therefore different types of installation and should not automatically be described as BS EN 14470-2 compliant.

Those installations should be designed according to the gases, quantities, ventilation, fire and explosion risks and relevant workplace guidance.

 

What are the BS EN 14470-2 fire resistance classifications?

BS EN 14470-2 classifies fire safety cabinets according to their performance during a prescribed fire-resistance test.

The four classifications are:

  • Type G15 – at least 15 minutes.
  • Type G30 – at least 30 minutes.
  • Type G60 – at least 60 minutes.
  • Type G90 – at least 90 minutes.

The Type G classification represents the tested fire performance of the complete cabinet design under the conditions specified by the standard.

It does not represent the fire resistance of the room or building in which the cabinet is installed.

 

Is Type G15 still included in BS EN 14470-2?

Yes. Type G15 remains one of the classifications within BS EN 14470-2:2006.

This differs from the current BS EN 14470-1:2023 standard for flammable-liquid cabinets, where the former Type 15 classification was removed.

The current BS EN 14470-2 classifications remain G15, G30, G60 and G90.

 

How is a BS EN 14470-2 cabinet fire tested?

BS EN 14470-2 includes a type test in which the complete gas cylinder cabinet is subjected to controlled external fire conditions.

The temperature at the gas cylinder valve is monitored during the test.

The Type G classification is determined by the period for which the temperature increase at the specified measuring location remains within the limit defined by the standard.

For example, a Type G90 cabinet must meet the required performance for at least 90 minutes under the prescribed test conditions.

This is a type test of the cabinet design rather than a fire test carried out on every individual cabinet manufactured.

 

What construction requirements does BS EN 14470-2 cover?

The standard addresses several aspects of cabinet design and performance, including:

  • Fire protection.
  • Cabinet construction.
  • Ventilation.
  • Gas cylinder restraint.
  • Safe insertion and removal of cylinders.
  • Installation of gas pipelines where cylinders remain in use.
  • Installation of electrical cables where appropriate.
  • Fire resistance.
  • Information supplied by the manufacturer.
  • Marking and labelling.

These requirements apply to the complete cabinet design rather than being independent product features.

 

Why must cylinders be restrained inside the cabinet?

Pressurised gas cylinders can create significant hazards if they fall or suffer damage to their valves, regulators or connections.

BS EN 14470-2 therefore includes requirements for securely restraining cylinders within the cabinet.

The cabinet should also enable cylinders to be safely moved into and out of position without compromising their stability.

Appropriate manual-handling procedures and employee training remain necessary even where a compliant cabinet is provided.

 

Does a BS EN 14470-2 cabinet need ventilation?

Yes. Ventilation is an integral consideration within BS EN 14470-2, and the Type G cabinet classifications require provision for connection to a ventilation system.

Suitable ventilation helps manage minor gas releases and reduce the likelihood of hazardous concentrations developing inside the cabinet.

This can be particularly important where gases are:

  • Flammable.
  • Toxic.
  • Oxidising.
  • Corrosive.
  • Asphyxiating.

The required extraction arrangement should be determined from the gas hazards, cabinet specification, manufacturer’s instructions and workplace risk assessment.

 

Why is gas cabinet ventilation important?

A leaking cylinder, valve or connection can release gas even when the quantity released is relatively small.

Depending on the gas, this may create:

  • A flammable or explosive atmosphere.
  • A toxic atmosphere.
  • Oxygen displacement and an asphyxiation risk.
  • Oxygen enrichment and increased fire risk.
  • A corrosive atmosphere.

Ventilation should therefore be treated as part of the complete cabinet installation rather than as an optional accessory selected independently of the gas hazards.

 

Can gas cylinders remain connected while inside the cabinet?

Yes. BS EN 14470-2 specifically recognises that pressurised gas cylinders can remain in use while stored inside the cabinet.

The standard therefore includes provisions for installing gas pipelines through the cabinet while maintaining the required safety performance.

Electrical cables may also be accommodated where appropriate.

The complete gas installation, including cylinders, regulators, connections and pipework, should be specified and installed by competent persons for the gases involved.

 

Does BS EN 14470-2 apply to every type of gas?

The standard establishes requirements for the cabinet, but the gases stored inside it can present very different hazards.

The risk assessment should consider whether cylinders contain gases that are:

  • Flammable.
  • Oxidising.
  • Toxic.
  • Corrosive.
  • Asphyxiating.
  • Otherwise hazardous under pressure.

Information from the gas supplier and Safety Data Sheet should be used to determine appropriate storage, segregation, ventilation and emergency measures.

 

Can incompatible gases be stored in the same cabinet?

Gas compatibility should be assessed before different cylinders are stored together.

The consequences of a simultaneous release may be significantly greater where incompatible gases are present in the same area.

Factors to consider include:

  • Flammable and oxidising gases.
  • Toxic gases.
  • Corrosive gases.
  • Possible reactions between released gases.
  • The number and size of cylinders.
  • Ventilation capacity.
  • Fire and explosion risks.

Use of a BS EN 14470-2 cabinet does not remove the need to consider segregation and compatibility.

 

Does HSE prefer gas cylinders to be stored outdoors?

Yes. HSE guidance states that cylinders not in use should generally be kept in safe, secure and uncongested outdoor locations where released gas can disperse readily and cannot accumulate in enclosed areas.

Indoor storage may be justified in particular circumstances, including safety, security, process quality or temperature-control requirements.

Where cylinders are stored indoors, HSE advises minimising the quantity and using a dedicated, well-ventilated and secure storeroom or cabinet of adequate fire-resisting construction.

 

When is an indoor gas cylinder cabinet appropriate?

An indoor gas cylinder cabinet may be appropriate where external storage is impracticable or where process requirements mean cylinders need to be located close to the point of use.

Examples can include:

  • Laboratories.
  • Research facilities.
  • Pharmaceutical facilities.
  • Manufacturing processes.
  • High-purity gas applications.
  • Processes where long gas lines could affect gas quality or operation.

The quantity of gas kept indoors should still be minimised and justified through the workplace risk assessment.

 

Does DSEAR apply to gas cylinder cabinets?

DSEAR may apply where a dangerous gas could create a fire, explosion or similar safety risk.

For flammable gases, the risk assessment should consider whether a release could form an explosive atmosphere.

Relevant factors include:

  • The gas involved.
  • Potential leak rates.
  • Ventilation.
  • Connection and disconnection activities.
  • Regulators and pipework.
  • Potential ignition sources.
  • The surrounding workplace.

Where an explosive atmosphere could occur, hazardous-area classification and suitable equipment may be required.

See our DSEAR Regulations 2002 guide.

 

Does storing a flammable gas cylinder automatically create an ATEX zone?

No. The presence of a flammable gas cylinder does not automatically mean that the entire room or cabinet is a hazardous zone.

The DSEAR assessment should determine whether an explosive atmosphere could occur, where it could occur and how frequently and for how long it may be present.

Ventilation, potential release points, cylinder connections and operating conditions all influence hazardous-area classification.

 

Does a BS EN 14470-2 cabinet make a workplace DSEAR compliant?

No. BS EN 14470-2 is a product standard for the cabinet, while DSEAR addresses the wider workplace risks created by dangerous substances.

Employers may also need to consider:

  • The gases and their hazardous properties.
  • The number and size of cylinders.
  • Ventilation.
  • Hazardous-area classification.
  • Ignition sources.
  • Gas detection where appropriate.
  • Gas compatibility and segregation.
  • Cylinder handling.
  • Inspection and maintenance.
  • Emergency arrangements.
  • Employee information and training.

A correctly specified cabinet can form part of these controls but does not make the complete workplace or gas installation automatically compliant.

 

How does BS EN 14470-2 differ from BS EN 14470-1?

The two parts of EN 14470 apply to different types of fire safety storage cabinet:

  • BS EN 14470-1 – fire safety storage cabinets for flammable liquids.
  • BS EN 14470-2 – fire safety storage cabinets for pressurised gas cylinders.

The fire classifications also differ. BS EN 14470-1:2023 uses Type 30, Type 60 and Type 90, while BS EN 14470-2:2006 uses Type G15, G30, G60 and G90.

A cabinet tested under one part should not automatically be assumed to meet the requirements of the other.

See our BS EN 14470-1:2023 guide for flammable-liquid cabinets.

 

What BS EN 14470-2 gas cylinder cabinets does Chemstore supply?

Chemstore supplies fire-rated gas cylinder cabinets designed for applications where pressurised gas cylinders need to be located indoors.

The range includes G30 and G90 BS EN 14470-2 cabinet options for laboratory, industrial and technical applications.


View Chemstore’s EN 14470-2 G90 fire-rated gas cylinder cabinets.

Chemstore also supplies fire-rated laboratory gas cylinder cabinets for applications requiring indoor cylinder storage close to the point of use.


View Chemstore’s EN 14470-2 G30 laboratory gas cylinder cabinets.

For larger quantities or applications where outdoor storage is more appropriate, Chemstore also supplies Gasvault gas cylinder stores.

Gasvault is a different type of storage solution from a BS EN 14470-2 cabinet and should not be described as compliant with BS EN 14470-2 unless a particular product has been tested and certified within the scope of that standard.

The appropriate storage solution should be selected according to the gases, cylinder quantities, location, fire and explosion risks, ventilation requirements and findings of the site-specific risk assessment.

 

Where can I find the official BS EN 14470-2 standard?

The current British Standard can be obtained from the British Standards Institution.

 

Important information

This page provides general information about BS EN 14470-2:2006 and does not reproduce or replace the standard itself. The complete standard should be obtained from the British Standards Institution where its detailed technical requirements are required.

This information does not replace DSEAR, HSE guidance, Safety Data Sheets, hazardous-area classification, a workplace risk assessment or advice from a competent person.